Home
» Schneider Electric » Low Voltage » Schneider GV6P500F

Schneider GV6P500F

0.00

The price is not final. Please check with the manager!

Schneider Electric Motor circuit breaker, TeSys GV6, 3P, 500A, Icu 36kA, thermal magnetic

Ask a Question

Datasheet

Main
Range of productTeSys GV6
RangeTeSys
Device short nameGV6P
Product nameTeSys GV6
TeSys Giga
Product or component typeMotor circuit breaker
Device applicationMotor protection
Trip unit technologyElectronic
Complementary
Poles description3P
Utilisation categoryCategory A conforming to IEC 60947-2
Motor power kW200…250 kW at 400/415 V AC 50/60 Hz
250…315 kW at 500 V AC 50/60 Hz
315…400 kW at 660/690 V AC 50/60 Hz
Breaking capacity36 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Control typeDirect rotary handle
[In] rated current500 A at 65 °C
Magnetic tripping current6500 A
[Ue] rated operational voltage690 V AC 50/60 Hz
[Ui] rated insulation voltage800 V AC 50/60 Hz conforming to IEC 60947-2
[Ith] conventional free air thermal current500 A conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage8 kV
Power dissipation per pole39.7 W
Mechanical durability15000 cycles
Electrical durability4000 cycles for AC-3 at 400/415 V In
Maximum operating rate25 cyc/h
Rated dutyContinuous
Connection pitch45 mm without spreaders
Connections – terminalsBars
Lugs
Tightening torque50 N.m M10 screw type
Mechanical robustnessVibrations: +/- 1 mm 2…13.2 Hz conforming to IEC 60068-2-6
Vibrations: 0.7 gn 13.2…100 Hz conforming to IEC 60068-2-6
Phase failure sensitivityYes conforming to IEC 60947-4-1
Height255 mm
Width140 mm
Depth179 mm
Net weight6.7 kg
ColourAnthracite (RAL 7016)
Suitability for isolationYes conforming to EN/IEC 60947-2
Environment
StandardsEN/IEC 60947-1
EN/IEC 60947-2
EN/IEC 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
Product certificationsIECEE CB Scheme
EAC (pending)
Climatic withstandconforming to IACS E10
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Ambient air temperature for storage-50…85 °C
Fire resistance960 °C conforming to IEC 60695-2-11
Operating altitude5000 m
Ambient air temperature for operation-25…70 °C
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height27.5 cm
Package 1 Width16.0 cm
Package 1 Length27.0 cm
Package 1 Weight5.98 kg
Unit Type of Package 2S04
Number of Units in Package 22
Package 2 Height30.0 cm
Package 2 Width40.0 cm
Package 2 Length60.0 cm
Package 2 Weight12.6 kg
Contractual warranty
Warranty18 months

Leave a Reply

Your email address will not be published. Required fields are marked *

Reviews