Datasheet
| Range | TeSys |
|---|---|
| Product name | TeSys GV7 |
| Product or component type | Circuit breaker |
| Device short name | GV7R |
| Device application | Motor |
| Poles description | 3P |
| Network type | AC |
| Utilisation category | AC-3 conforming to IEC 60947-4-1 |
| Network frequency | 50/60 Hz conforming to IEC 60947-4-1 |
| Breaking capacity | 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| thermal protection adjustment range | 30…50 A |
| Trip unit technology | Thermal-magnetic |
| Mounting mode | By clips By screws |
|---|---|
| Mounting support | Rail Kit for fixing the switchgear Flush Panel mounting |
| Mounting position | Vertical |
| Motor power kW | 22 kW at 400…415 V AC 50/60 Hz 30 kW at 500 V AC 50/60 Hz 30 kW at 660…690 V AC 50/60 Hz |
| Control type | Rocker lever |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 750 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ith] conventional free air thermal current | 50 A conforming to IEC 60947-4-1 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
| power dissipation per pole | 5 W |
| Power dissipation per pole | 5 W |
| Mechanical durability | 50000 cycles |
| Electrical durability | 30000 cycles for AC-3 at 440 V In 50000 cycles for AC-3 at 440 V In/2 |
| Maximum operating rate | 25 cyc/h |
| Rated duty | Continuous conforming to IEC 60947-4-1 |
| Connection pitch | 35 mm without spreaders 45 mm with spreaders |
| Connections – terminals | Bars Cable with lug – external diameter: 10 mm Screw Bare cable connectors 1.5…95 mm² |
| Tightening torque | 10 N.m on screw M6 screw type 15 N.m on bare cable connectors for cable 1.5…95 mm² |
| Mechanical robustness | Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations: 2.5 Gn, 0…25 Hz conforming to IEC 60068-2-6 |
| Suitability for isolation | Yes conforming to IEC 60947-1 |
| Phase failure sensitivity | Yes conforming to IEC 60947-4-1 § 7-2-1-5-2 |
| Height | 161 mm |
| Width | 105 mm |
| Depth | 111 mm |
| Net weight | 2.015 kg |
| Standards | EN/IEC 60947-2 NF C 79-130 EN/IEC 60947-1 EN/IEC 60947-4-1 NF C 63-650 VDE 0660 VDE 0113 NF C 63-120 |
|---|---|
| Product certifications | DNV UL |
| Protective treatment | TC |
| IP degree of protection | IP405 conforming to IEC 60529 (with terminal shrouds) |
| Pollution degree | 3 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -55…95 °C |
| Fire resistance | 960 °C conforming to IEC 60695-2-1 |
| Operating altitude | 2000 m |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 11.5 cm |
| Package 1 Width | 14 cm |
| Package 1 Length | 17.5 cm |
| Package 1 Weight | 1.924 kg |
| Warranty | 18 months |
|---|