Schneider ATV61HD11Y

0.00

The price is not final. Please check with the manager!

Schneider Electric variable speed drive ATV61 – 11kW / 690V – 10HP / 575V – IP20

Ask a Question

Datasheet

Main
Range of productAltivar 61
Product or component typeVariable speed drive
Product specific applicationPumping and ventilation machine
Component nameATV61
Motor power kW11 kW, 3 phases at 690 V
7.5 kW, 3 phases at 500 V
Motor power hp10 hp, 3 phases at 575 V
power supply voltage500…690 V – 15…10 %
supply number of phases3 phases
Line current12.3 A for 600 V 3 phases 7.5 kW / 10 hp
14.6 A for 500 V 3 phases 7.5 kW / 10 hp
15.5 A for 690 V 3 phases 7.5 kW / 10 hp
EMC filterLevel 3 EMC filter
Assembly styleWith heat sink
maximum prospective line Isc22 kA for 3 phases
Maximum transient current16.2 A for 60 s, 3 phases
Nominal switching frequency4 kHz
Switching frequency2.5…6 kHz adjustable
4…6 kHz with derating factor
asynchronous motor controlVoltage/frequency ratio, 5 points
Voltage/frequency ratio, 2 points
Flux vector control without sensor, standard
Voltage/frequency ratio – Energy Saving, quadratic U/f
Synchronous motor control profileVector control without sensor, standard
communication port protocolModbus
CANopen
Type of polarizationNo impedance for Modbus
Option cardCommunication card for APOGEE FLN
Communication card for BACnet
Communication card for CC-Link
Controller inside programmable card
Communication card for DeviceNet
Communication card for EtherNet/IP
Communication card for Fipio
I/O extension card
Communication card for Interbus-S
Communication card for LonWorks
Communication card for METASYS N2
Communication card for Modbus Plus
Communication card for Modbus TCP
Communication card for Modbus/Uni-Telway
Multi-pump card
Communication card for Profibus DP
Communication card for Profibus DP V1
Complementary
Product destinationSynchronous motors
Asynchronous motors
power supply voltage limits425…759 V
power supply frequency50…60 Hz – 5…5 %
power supply frequency limits47.5…63 Hz
Continuous output current11 A at 4 kHz, 575 V – 3 phases
13.5 A at 4 kHz, 500 V – 3 phases
13.5 A at 4 kHz, 690 V – 3 phases
Output frequency0.1…500 Hz
Speed range1…100 in open-loop mode, without speed feedback
Speed accuracy+/- 10 % of nominal slip 0.2 Tn to Tn without speed feedback
Torque accuracy+/- 15 % in open-loop mode, without speed feedback
Transient overtorque130 % of nominal motor torque +/- 10 % for 60 s
Braking torque<= 125 % with braking resistor
30 % without braking resistor
Regulation loopFrequency PI regulator
Motor slip compensationNot available in voltage/frequency ratio (2 or 5 points)
Adjustable
Automatic whatever the load
Can be suppressed
diagnostic1 LED (red) for drive voltage
Output voltage<= power supply voltage
electrical isolationBetween power and control terminals
type of cable for mounting in an enclosureWith an IP21 or an IP31 kit: 3 wire(s)IEC cable at 40 °C, copper 70 °C / PVC
With UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR
Electrical connectionTerminal 2.5 mm² / AWG 14 (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1…LI6, PWR)
Terminal 50 mm² / AWG 1/0 (L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB)
Tightening torque0.6 N.m (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1…LI6, PWR)
12 N.m, 102.2 lb.in (L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB)
SupplyInternal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC, +/- 5 %, <10 mA with overload and short-circuit protection
Internal supply: 24 V DC (21…27 V), <200 mA with overload and short-circuit protection
External supply: 24 V DC (19…30 V)
Analogue input number2
Analogue input typeAI1-/Al1+ bipolar differential voltage: +/- 10 V DC 24 V max, resolution 11 bits + sign
AI2 software-configurable current: 0…20 mA, impedance: 242 Ohm, resolution 11 bits
AI2 software-configurable voltage: 0…10 V DC 24 V max, impedance: 30000 Ohm, resolution 11 bits
sampling time2 ms +/- 0.5 ms (AI1-/Al1+) – analog input
2 ms +/- 0.5 ms (Al2) – analog input
2 ms +/- 0.5 ms (AO1) – analog output
2 ms +/- 0.5 ms (LI1…LI5) – discrete input
2 ms +/- 0.5 ms (LI6)if configured as logic input – discrete input
absolute accuracy precision+/- 0.6 % (AI1-/Al1+) for a temperature variation 60 °C
+/- 0.6 % (AI2) for a temperature variation 60 °C
+/- 1 % (AO1) for a temperature variation 60 °C
Linearity error+/- 0.15 % of maximum value (AI1-/Al1+)
+/- 0.15 % of maximum value (AI2)
+/- 0.2 % (AO1)
Analogue output number1
Analogue output typeAO1 software-configurable current, analogue output range 0…20 mA, impedance: 500 Ohm, resolution 10 bits
AO1 software-configurable voltage, analogue output range 0…10 V DC, impedance: 470 Ohm, resolution 10 bits
AO1 software-configurable logic output 10 V, 20 mA
Discrete output number2
Discrete output typeConfigurable relay logic: (R1A, R1B, R1C) NO/NC – 100000 cycles
Configurable relay logic: (R2A, R2B) NO – 100000 cycles
maximum response time<= 100 ms in STO (Safe Torque Off)
R1A, R1B, R1C <= 7 ms, tolerance +/- 0.5 ms
R2A, R2B <= 7 ms, tolerance +/- 0.5 ms
Minimum switching current3 mA at 24 V DC for configurable relay logic
Maximum switching currentR1, R2: 2 A at 250 V AC inductive load, cos phi = 0.4 and L/R = 7 ms
R1, R2: 2 A at 30 V DC inductive load, cos phi = 0.4 and L/R = 7 ms
R1, R2: 5 A at 250 V AC resistive load, cos phi = 1 and L/R = 0 ms
R1, R2: 5 A at 30 V DC resistive load, cos phi = 1 and L/R = 0 ms
Discrete input number7
Discrete input typeProgrammable (LI1…LI5)24 V DC (<= 30 V), with level 1 PLC – 3500 Ohm
Switch-configurable (LI6)24 V DC (<= 30 V), with level 1 PLC – 3500 Ohm
Switch-configurable PTC probe (LI6)0…6 probes – 1500 Ohm
Safety input (PWR)24 V DC (<= 30 V) – 1500 Ohm
Discrete input logicNegative logic (sink) (LI1…LI5), > 16 V (state 0), < 10 V (state 1)
Positive logic (source) (LI1…LI5), < 5 V (state 0), > 11 V (state 1)
Negative logic (sink) (LI6)if configured as logic input, > 16 V (state 0), < 10 V (state 1)
Positive logic (source) (LI6)if configured as logic input, < 5 V (state 0), > 11 V (state 1)
Acceleration and deceleration rampsLinear adjustable separately from 0.01 to 9000 s
S, U or customized
Automatic adaptation of ramp if braking capacity exceeded, by using resistor
Braking to standstillBy DC injection
Protection typeAgainst exceeding limit speed: drive
Against input phase loss: drive
Break on the control circuit: drive
Input phase breaks: drive
Line supply overvoltage: drive
Line supply undervoltage: drive
Overcurrent between output phases and earth: drive
Overheating protection: drive
Overvoltages on the DC bus: drive
Power removal: drive
Short-circuit between motor phases: drive
Thermal protection: drive
Motor phase break: motor
Power removal: motor
Thermal protection: motor
Insulation resistance> 1 mOhm 500 V DC for 1 minute to earth
Frequency resolutionAnalog input: 0.024/50 Hz
Display unit: 0.1 Hz
Connector type1 RJ45 (on front face) for Modbus
1 RJ45 (on terminal) for Modbus
Male SUB-D 9 on RJ45 for CANopen
Physical interface2-wire RS 485 for Modbus
Transmission frameRTU for Modbus
Transmission rate4800 bps, 9600 bps, 19200 bps, 38.4 Kbps for Modbus on terminal
9600 bps, 19200 bps for Modbus on front face
20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps for CANopen
Data format8 bits, 1 stop, even parity for Modbus on front face
8 bits, odd even or no configurable parity for Modbus on terminal
Number of addresses1…127 for CANopen
1…247 for Modbus
Method of accessSlave CANopen
MarkingCE
Operating positionVertical +/- 10 degree
Net weight30 kg
Width240 mm
Height420 mm
Depth236 mm
Environment
Noise level59.9 dB conforming to 86/188/EEC
Dielectric strength3110 V DC between earth and power terminals
5345 V DC between control and power terminals
Electromagnetic compatibilityConducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
StandardsEN 61800-3 environments 1 category C3
UL Type 1
IEC 60721-3-3 class 3C2
EN 61800-3 environments 2 category C3
EN/IEC 61800-5-1
EN 55011 class A group 2
EN/IEC 61800-3
Product certificationsUL
DNV
GOST
NOM 117
CSA
C-Tick
Pollution degree3 conforming to EN/IEC 61800-5-1
3 conforming to UL 840
degree of proctectionIP20 on upper part without blanking plate on cover conforming to EN/IEC 60529
IP20 on upper part without blanking plate on cover conforming to EN/IEC 61800-5-1
IP21 conforming to EN/IEC 60529
IP21 conforming to EN/IEC 61800-5-1
IP41 on upper part conforming to EN/IEC 60529
IP41 on upper part conforming to EN/IEC 61800-5-1
IP54 on lower part conforming to EN/IEC 60529
IP54 on lower part conforming to EN/IEC 61800-5-1
Vibration resistance1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-6
1.5 mm peak to peak (f= 3…13 Hz) conforming to EN/IEC 60068-2-6
Shock resistance15 gn for 11 ms conforming to EN/IEC 60068-2-27
Relative humidity5…95 % without condensation conforming to IEC 60068-2-3
5…95 % without dripping water conforming to IEC 60068-2-3
Ambient air temperature for operation-10…50 °C (without derating)
50…60 °C (with derating factor)
Ambient air temperature for storage-25…70 °C
Operating altitude<= 1000 m without derating
1000…2260 m with current derating 1 % per 100 m
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height37.0 cm
Package 1 Width40.0 cm
Package 1 Length60.0 cm
Package 1 Weight31.5 kg
Unit Type of Package 2P06
Number of Units in Package 22
Package 2 Height77.0 cm
Package 2 Width60.0 cm
Package 2 Length80.0 cm
Package 2 Weight72.0 kg
Contractual warranty
Warranty18 months

Leave a Reply

Your email address will not be published. Required fields are marked *

Reviews