Datasheet
| Range compatibility | Altivar 61 Altivar 71 |
| [Us] rated supply voltage | 400 V (+/- 10 %) |
| Power supply frequency | 50 Hz (tolerance: +/- 2 %) |
| Quantity per drive | 1 filter per drive for variable speed drive ATV71Q motor : 132 kW / 200 hp 1 filter per drive for variable speed drive ATV61Q motor : 132 kW / 200 hp 1 filter per drive for variable speed drive ATV71H motor : 132 kW / 200 hp 1 filter per drive for variable speed drive ATV61H motor : 132 kW / 200 hp |
| [In] rated current | 225 A for output 217 A for input |
| Network number of phases | 3 phases |
| THDI | 5 % for variable speed drive ATV71Q motor : 132 kW / 200 hp 5 % for variable speed drive ATV61Q motor : 132 kW / 200 hp 5 % for variable speed drive ATV71H motor : 132 kW / 200 hp 5 % for variable speed drive ATV61H motor : 132 kW / 200 hp |
| Max current | 1.5 x nominal current (duration = 60 s) |
| Efficiency | <= 98=”” td=””> |
| Thermal losses | 1194 W |
| Cos phi | 0.99 at 100 % of line current 0.85 at 75 % of line current 1 at 150 % of line current |
| Electrical connection | X1-1…X2-3 terminal, connection capacity: 25…300 mmВІ A, B terminal, connection capacity: 2.5 mmВІ |
| Electrical insulation class | Class F |
| Device Full Name | Schneider Electric VW3A46133 |